9 – 65
Indicators
Utilizing the programmable DAS function of the COM35:
The COM35, exclusively, provides the ability to activate the DAS function of the WLETU776 directly via the COM35’s programmable I/O.
When the COM35 is programmed to enable this function, opening the connection between terminals 1 and 3 will cause the trip unit to switch
to Parameter Set B. When contact is made between these two terminals, the trip unit will utilize Parameter Set A. The programmable output
can then be used to activate a local status indicator (as illustrated). This COM35 I/O functionality must be programmed by the user via
Siemens powerconfig software.
The programable output can carry a load of 1A, up to an ambient temperature of 45C (113F). Above that, the current–carrying capability of
the output should be de-rated to 400mA at 70C (158F). The length of the wires connecting the activation switch to the input of the COM35
should be less than 50m (165ft) and be AWG18. Twisted/shielded-pair wiring is recommended for cable runs approaching this length.
LED
Indication Meaning
PROFINET IO
green
Normal PROFINET IO communcation
green
flashing
Communication with PROFINET IO
Controller, no communication with
PROFINET IO Supervisor
red
No communication with PROFINET IO
Controller, no communication with
PROFINET IO Supervisor
Modbus TCP
green
At least one opened Modbus TCP
connection
green
flashing
Ethernet link available but no Modbus
TCP connection
off
No Ethernet link
c
off
No
c
participant active
green
c
communication operating
green
flashing
No ETU installed (e.g: non-automatic/
disconnect switch application)
red
c
error
DAS switch
ON/OFF
DAS Status indicator
24V DC
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......