9 – 95
9.2.3.5 Analog output module
Function
With the analog output module, analog measured values can be transmitted, which can be shown on the cubicle door by means
of moving-coil instruments. A total of 4 outputs is available.
For the output signal, two different formats can be selected:
- 4 - 20 mA, output via terminal strip X5
- 0 - 10 V, output via terminal strip X4
Installation
Connection
A maximum of 2 analog output modules can be connected; the rotary coding switches of these modules must, however, have different
settings.
Terminal assignment
Settings
The measured values to be signaled are adjusted using the rotary switch. They are always present on the two terminal strips in the
corresponding format.
The following values are available at the outputs:
Output assignment
Position
AO 1
AO 2
AO 3
AO 4
I
I
L1
I
L2
I
L3
I
N
U
U
L12
U
L23
U
L31
U
L1N
P
P
L1
P
L2
P
L3
S
total
f
f
U
LLavg
P
total
P.F.
avg
P.F.
P.F.
L1
P.F.
L2
P.F.
L3
Phase unbalance current in%
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......