9 – 15
Short-time delayed short-circuit protection switchable to I
2
t
Trip units ETU745 - 776 make it possible to switch over from a constant delay time to an I
2
t-characteristic. In this way, the delay time
depends on the short-circuit current, but with a constant I
2
t
sd
-value, providing better coordination with downstream fuses.
In this case, the setting options for the short-time delay t
R
are as follows:
Switchover to the I
2
t
sd
characteristic can be made via:
- the t
sd
rotary coding switch (ETU745); this must be set to a value in the white area.
.
- the graphical display (ETU776)
- TD400 and the software "powerconfig"
- the COM modules with a PC with the software “powerconfig” installed
Changeable parameter sets
The trip unit ETU776 contains two complete sets of protective parameters and can be switched between them locally or remotely.
This enables lowering instantaneous and short-time settings for arc flash mitigation as well as changing parameters when the source
of supply changes between utility and generator.
Switching between parameter sets can be made manually via:
- the graphical display (ETU776)
or remotely via:
- the
Cublicle
BUS
with an input signal at the digital input module.
- the PROFIBUS DP
- the PROFINET IO, Modbus TCP and Modbus RTU.
Settings for t
sd
ETU745
t
sd
= 0.1 / 0.2 / 0.3 / 0.4 sec. (at 12 x I
n
)
ETU776
t
sd
= 0.1 - 0.4 sec. (at 12 x I
n
)
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......