
9 – 14
Thermal memory can be switched On/Off
Trip units ETU745 - 776 make it possible to continue with the internally calculated reproduction of the thermal processes in downstream
switchgear and consumers even if the circuit breaker is open and the electronic system has no external supply. In this way, an effective
protection against thermal overload can also be guaranteed for frequent closing and opening processes.
The thermal memory can be activated via:
- a slide switch (ETU745)
- the graphical display (ETU776)
- TD400 and the software "powerconfig"
- the COM modules with a PC with the software “powerconfig” installed
Zone selective interlocking
If the circuit breaker is combined with a ZSI module
, a short-circuit occurring in systems with several grading levels can be
precisely localized.
For this purpose, all circuit breakers are interconnected through their ZSI-modules.
When a short-circuit occurs, each circuit breaker affected by the short-circuit current queries its downstream circuit breaker to determine
whether the short-circuit is also present in the next downstream grading level. In the direction of the energy flow, only the circuit breaker
nearest to the short-circuit is tripped. A delay time which may have been set for the short-circuit tripping is deactivated. However, tripping
takes place after 50 milliseconds at the earliest.
Overload protection switchable to I
4
t
The trip units ETU776 and ETU745 can be set to perform long-time protection using either I
2
t or I
4
t. I
4
t will yield faster tripping times and will
improve coordination with many types of fuses. The ETU745 can be switched between the two modes via a slide switch and the ETU776 via
a menu setting.
In this case, the setting options for the long delay time t
R
change as follows:
Setting values for t
R
ETU745
t
R
= 1 / 2 / 3 / 4 / 5 sec. (at 6 x I
R
)
ETU776
t
R
= 1- 5 sec. (at 6 x I
R
)
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......