9 – 82
9.2.2.7 Connecting voltage transformers
The metering module ("Meter
PLUS
Function") can be set to expect 3W or 4W (LL/LG) connections and will correct the amplitude and phase
of the signal as necessary.
The parameters on the trip unit must be set as follows:
(1)
VT Primary voltage (100 V ac ... 1200 V ac)
(2)
VT Secondary voltage
(100 V/110 V/120 V)
(3)
VT Connection
(Wye / LG, Delta / LL)
Three VTs must be used at all times.
All three VTs must be rated for the rated LL voltage (e.g. 480 V) and can have either 100 V / 110 V or 120 V secondary rated voltage.
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this equipment before working on this device.
Note:
Required primary and secondary overcurrent protection (fusing) not shown for clarity.
to X8.8
to X8.7
to X8.6
to X8.5
L1
L2
L3
LN
120V/ 3
primary bus
configuration
VT primary
connection
VT primary
connection
3:4W System: Wye (L-N, L-G) Connection
V
L-L
(V
L-L
)/ 3
(V
L-L
)/ 3
Secondary
Primary
(277V)
(69V)
(assuming 480V LL)
V
L-L
(480V)
120V
Metering VT Settings:
Delta/Wye : Delta
VT Primary: 480 (for instance)
VT Secondary: 120 (for instance)
Metering VT Settings:
Delta/Wye : Wye
VT Primary: 480 (for instance)
VT Secondary: 120 (for instance)
primary bus
configuration
69V
√
√
√
Secondary
to X8.8
to X8.7
to X8.6
to X8.5
L1
L2
L3
V
1-2
120V
V
2-3
V
3-1
Primary
V
L-L
3
:
3W System: Delta (L-L) Connection
Rotation: A-C-B
(assuming 480V LL)
(480V)
208V
Secondary
to X8.8
to X8.7
to X8.6
to X8.5
L1
L2
L3
V
1-2
120V
V
2-3
V
3-1
Primary
V
L-L
3
:
3W System: Delta (L-L) Connection
Rotation: A-B-C
(assuming 480V LL)
(480V)
208V
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......