27 – 7
WL Circuit Break er
Function ov erview of the electronic trip units
Basic Functions
ETU745
Long-time overcurrent protection
Function can be switched ON/OFF
–
Setting range
IR = In x …
0.4, 0.45, 0.5, 0.55, 0.6,
0.65, 0.7, 0.8, 0.9, 1
Switch-selectable overload protection
(
I2t or I4t dependent function)
Setting range of
time
delay class
tR at I
2t
(seconds)
2, 3.5, 5.5, 8, 10,
14, 17, 21, 25, 30
Setting range of
tR at I
4t
(seconds)
1, 2, 3, 4, 5
Thermal memor
(via (on/off via key pad or communications)
(on/off via key pad or communications)
slide switch)
Phase loss sensitivity
at tsd=20ms (M)
N-conductor protection
Function can be switched ON/OFF
(via slide switch)
N-conductor setting range
IN = In x
0.5 … 1
Short-time delayed overcurrent protection
Function can be switched ON/OFF
(via rotary switch)
Setting range
Isd = In x …
1.25, 1.5, 2, 2.5,
3, 4, 6, 8, 10, 12
Setting range of
tsd, fixed
(seconds)
0.02 (M), 0.1, 0.2,
0.3, 0.4, OFF
Switch-selectable short-time delayed
short-circuit protection
(
I2t dependent function)
(via rotary coding switch)
Setting range of
tsd at I
2t
(seconds)
0.1, 0.2, 0.3, 0.4
Zone Selective Interlocking (ZSI) function
per CubicleBUS module
Instantaneous overcurrent protection
Function can be switched ON/OFF,
Extended Instantaneous Protection
is enabled when OFF
(via rotary coding switch)
Setting range
Ii = In x …
1.5, 2.2, 3, 4, 6, 8, 10, 12
0.8 x
I
cw
= max, OFF=
I
cw
=EIP
Ground fault protection
O
(field installable module)
Trip and alarm function
Detection of the ground fault current
by residual summing method
Detection of the ground fault current
by direct summing method
Setting range of the
Ig for trip
, B, C, D, E (100… 1200A)
Setting range of the
Ig for alarm
A,
A,
B, C, D, E (100… 1200A)
Setting range of the
tg
(seconds)
0.1, 0.2, 0.3, 0.4, 0.5
Switch-selectable
ground fault protection
(
I2t / fixed)
Setting range
tg at I
2t
0.1, 0.2, 0.3, 0.4, 0.5
ZSI ground function
per CubicleBUS module
L
N
S
I
G
3
In
2
time
delay
time
delay
time
delay
time
delay
time
delay
ETU776
–
40-100% of In (Adjustable in Amps )
2 … 30 (step: 0.1s)
1 … 5 (step: 0.1s)
(via key pad or communications)
(via key pad or communications)
(via key pad or communications)
(via key pad or communications)
(via key pad or communications)
0.5 … 2, OFF
1.25 … 0.8 x Icw = max
(step: 10A)
M, 0.08 … 0.4, OFF (step: 0.001s)
0.1 … 0.4 (step: 0.001s)
per CubicleBUS module
1.5 x
I
n
… 0.8 x
I
cs
= max, OFF=
I
cw
=EIP
O
(field installable module)
A … E (step: 1A)
A … E (step: 1A)
0.1 … 2.0 (step: 0.001s)
0.1 … 2.0 (step: 0.001s)
per CubicleBUS module
1
1
available
–
not available
O
optional
Extended Instantaneous Protection (EIP) allows the WL circuit breaker to be applied at the withstand rating of
the circuit breaker with minus 0% tolerance; this means there is no instantaneous override at all. EIP further
enables the circuit breaker to be applied up to the full instantaneous rating of the circuit breaker in systems
where the available fault current exceeds the withstand rating.
2
Note: ETU776 settings via communications: 10A steps for Instantaneous and Short Time pickup, all others 1A steps.
Via ETU Keypad: Below 1000A: 10A steps 1000A-1600A: 50A steps
1600A-10000A: 100A steps Above 10000A, 1000A steps
1
Notes:
M
= Motor protection setting indicates phase loss sensitivity is enabled. LT pick-up reduced 80% when phase unbalance > 50%. ST = 20 ms
Communications
= Setting the parameters of the trip unit via the Breaker Data Adapter, MODBUS, or PROFIBUS
Key pad
= Direct input
the trip unit
on
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......