5 – 8
5.1.3.3 Draw-out circuit breaker
Without arc chute cover
A
Minimum vertical clearance
B
Minimum clearance on either side
C
Minimum horizontal rear-side clearance
1) Measured from top surface of arc chutes
2) Valid with unblocked arcing space on top only
3) Class C with phase barriers made of insulating material only
u
Minimum clearance to live parts
v
Minimum clearance to grounded metal parts
c
Minimum clearance to non-conductive parts
With arc chute cover
Arc chute covers for draw-out cradles are options for every frame size. The gases are directed to the side outlets of the cradle.
Openings to the outside provided on the sides of the cradle shall not be blocked. Ventilation openings on the upper rear ensure that
no gas can escape upwards.
FS
Class
3)
Dimensions
(mm)
A
1)
B
C
u
v, c
u
2)
v, c
u
2)
v, c
Operating voltage
(V)
480
600
480
600
480
600
480
600
480
600
480
600
I
S, H, L
Consult Technical Support
II
S
150
300
100
100
20
50
10
10
14
14
10
10
II
L
250
600
100
100
50
100
10
10
14
30
10
10
III
L
250
500
100
100
50
100
10
10
14
14
10
10
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......