9 – 16
Ground-fault protection switchable to I
2
t characteristic
The ground-fault protection modules for trip units ETU745 - 776 make it possible to switch over from a constant delay time to an
I
2
t characteristic.
This provides an inverse-time tripping characteristic with a constant I
2
t
g
value, providing better selectivity of the ground-fault protection in
systems with several grading levels.
The setting options for the delay time remain unchanged.
Switchover to the I
2
t
g
characteristic can be made via:
- the t
g
rotary coding switch (ETU745);
this must be set to a value in the white area.
- the graphical display (ETU776)
- TD400 and the software "powerconfig"
- the COM modules with a PC with the software “powerconfig” installed
Ground-fault alarm
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......