HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.5.7.3
Amount
Define the filling amount. The
valve will be closed and filling
stopped when defined amount is
reached.
1.0
[kg]
User
2.5.7.3
Amount
Define the filling amount. The
valve will be closed and filling
stopped when defined amount is
reached.
1.0
L
User
2.5.7.3
Amount
Define the filling amount. The
valve will be closed and filling
stopped when defined amount is
reached.
1.0
SL
User
2.5.7.4
Decimal Places
Define the decimal point for the
process value displayed in the
Local User Interface.
2
● Auto
● No decimal
place
● 1
● 2
● 3
● 4
● 5
● 6
User
2.5.7.5
Calibration
2.5.7.5.2
Fixed Compensation
Define the fixed pre-stop value.
The value is subtracted from
"Amount" to compensate for ap‐
plication delays in closing the
valves.
[kg]
User
2.5.7.5.2
Fixed Compensation
Define the fixed pre-stop value.
The value is subtracted from
"Amount" to compensate for ap‐
plication delays in closing the
valves.
L
User
2.5.7.5.2
Fixed Compensation
Define the fixed pre-stop value.
The value is subtracted from
"Amount" to compensate for ap‐
plication delays in closing the
valves.
SL
User
2.5.7.6
Valve Control
2.5.7.6.1
Stage Setup Format
Specify if valve control parame‐
ters are defined as absolute or
relative values (% of dosing
amount).
Relative
● Relative
● Absolute
User
2.5.7.6.2
Stage 1 Primary Open
Define the dosing amount value
to open the primary valve. The
value is in % of defined dosing
amount.
0
[%]
0.0 to 100.0
User
Default settings
E.6 Dosing
FC430 (From firmware 4.0)