HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.4.5.4.1
Process value
Select process value for current
output.
Mass flow
● Mass flow
● Volume flow
● Standard
volume flow
● Density
● Standard
density
● Medium
temperature
● Fraction A
● Fraction B
● Fraction A %
● Fraction B %
● Control valve
User
2.4.5.4.2
Direction
Select measured flow direction.
The flow meter will only output
current when flow value is meas‐
ured in selected direction.
Positive
● Positive
● Negative
● Bidirectional
● Symmetric
User
2.4.5.4.3
Loop current scale
● 4 to 20 mA
NAMUR
● 4 to 20 mA US
● 4 to 20 mA
(fault = 0 mA)
● 4 to 20 mA
● 0 to 20 mA
User
2.4.5.4.4
Upper range value
Assign process value to the
nominal upper range value
1)
1)
User
2.4.5.4.5
Lower range value
Assign process value to the
nominal lower range value
1)
1)
User
2.4.5.4.6
Damping value
Set filter time constant. Defines
the damping of the current out‐
put signal. 0.0 means filter is off
0 s
● 0 to 100 s
User
2.4.5.4.7
Fail-safe behavior
Select current output reaction in
case of a fault.
Lower fault cur‐
rent
● Lower fault
current
● Upper fault
current
● Last valid
value
● Current value
● Fail safe value
User
Default settings
E.5 Inputs and outputs
FC430 (From firmware 4.0)
400
Operating Instructions, 06/2017, A5E39789392-AA