HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.4.5.4.8
Fail-safe value
Define fail-safe current output
value if 'Fail-safe behaviour' pa‐
rameter is set to ’Fail-safe value’.
3.5 mA
● 0 to 25 mA
User
2.4.5.4.9
Fail-safe minimum time Minimum time the output stays
in fail-safe mode. Short events
will be prolonged.
0 s
● 0 to 100 s
user
2.4.5.6
Frequency output
2.4.5.6.1
Process value
Mass flow
● Mass flow
● Volume flow
● Standard
volume flow
● Density
● Standard
density
● Medium
temperature
● Fraction A
● Fraction B
● Fraction A %
● Fraction B %
● Control valve
User
2.4.5.6.2
Direction
Select measured flow direction.
The flow meter will only output
current when flow value is meas‐
ured in selected direction.
Positive
● Positive
● Negative
● Bidirectional
● Symmetric
User
2.4.5.6.3
Frequency value high
Assign maximum frequency val‐
ue
10000
● 0 to 12500 Hz User
2.4.5.6.4
Frequency value low
Assign minimum frequency val‐
ue
0 Hz
● 0 to 12500 Hz User
2.4.5.6.5
Upper range value
Assign process value to the
nominal upper range value
1)
1)
User
2.4.5.6.6
Lower range value
Assign process value to the
nominal lower range value
1)
1)
User
2.4.5.6.7
Damping value
Set filter time constant. Defines
the damping of the current out‐
put signal. 0.0 means filter is off
0 s
● 0 to 100 s
User
Default settings
E.5 Inputs and outputs
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
401