HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.3.3.10.12)
Upper alarm limit
Set upper alarm limit. Alarm is
triggered if totalizer 3 value is
above the limit.
[m
3
]
User
2.3.3.10.22)
Upper warning limit
Set upper warning limit. Waning
is triggered if totalizer 3 value is
above the limit.
[m
3
]
User
2.3.3.10.32)
Lower warning limit
Set lower alarm limit. Warning is
triggered if totalizer 3 value is
above the limit.
[m
3
]
User
2.3.3.10.4 2)
Lower alarm limit
Set lower warning limit. Alarm is
triggered if totalizer 3 value is
above the limit.
[m
3
]
User
2.3.3.10.5 2)
Hysteresis
Enter the hysteresis to avoid un‐
wanted rapid switching.
0
[m
3
]
User
2.3.3.10.3)
Upper alarm limit
Set upper alarm limit. Alarm is
triggered if totalizer 3 value is
above the limit.
[normal m
3
]
User
2.3.3.10.23)
Upper warning limit
Set upper warning limit. Waning
is triggered if totalizer 3 value is
above the limit.
[normal m
3
]
User
2.3.3.10.33)
Lower warning limit
Set lower alarm limit. Warning is
triggered if totalizer 3 value is
above the limit.
[normal m
3
]
User
2.3.3.10.4
3
)
Lower alarm limit
Set lower warning limit. Alarm is
triggered if totalizer 3 value is
above the limit.
[normal m
3
]
User
2.3.3.10.5
3
)
Alarm Hysteresis
Sets the hysteresis for alarm
and warning limits. The hystere‐
sis is the distance between the
limits for activation and deactiva‐
tion of an alarm/warning.
0
[normal m
3
]
User
2.3.4
Reset all totalizers
Reset totalizer 1, totalizer 2 and
totalizer 3 to zero
Cancel
● Cancel
● Ok
User
1)
Process Value is set to Mass flow
2)
Process Value is set to Volume flow
3)
Process Value is set to Standard volume flow
Default settings
E.4 Totalizer
FC430 (From firmware 4.0)
344