HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.5.7.6.7
Partially Open Current
Level
Define current level to partly
close the analog valve.
10
[mA]
0 to 20
User
2.5.7.6.8
Fully Open Current Lev‐
el
Define current level to fully open
the analog valve.
20
[mA]
0 to 20
User
2.5.7.6.9
Fully Open
Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
[%]
0.0 to100.0
User
2.5.7.6.10
Partially Closed
Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
0.0
[%]
0.0 to100.0
User
2.5.7.6.9
Fully Open
Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
[kg]
User
2.5.7.6.10
Partially Closed
Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
1.0
[kg]
User
2.5.7.6.9
Fully Open
Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
L
User
2.5.7.6.10
Partially Closed
Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
1.0
L
User
2.5.7.6.9
Fully Open
Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
SI
User
2.5.7.6.10
Partially Closed
Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
1.0
SI
User
2.5.7.7
Fault Handling
2.5.7.7.1
Duration mode
Enable or disable dosing time
supervision. An alarm is raised
and valve(s) closed if dosing
time is exceeded.
Off
● Off
● On
User
2.5.7.7.2
Duration time
Define the supervision time. An
alarm is raised and valve(s)
closed if dosing time is excee‐
ded.
3600
1 to 360000
User
2.5.7.7.3
Overrun mode
Enable or disable dosing
amount supervision. An alarm is
raised and valve(s) closed if dos‐
ing amount is exceeded.
Off
● Off
● On
User
2.5.7.7.4
Overrun value
Define the dosing overrun
amount. An alarm is raised and
valve(s) closed if dosing amount
is exceeded.
0
User
Default settings
E.6 Dosing
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
443