3RW3 semiconductor motor control unit
SIRIUS System Manual
8-52
GWA 4NEB 430 0999-02b
8.7.5 Specifications in acc. with NEMA
The specified motor ratings are guide values.
The soft starter must be selected on the basis of the rated current I
e
.
The motor ratings are based on the values specified in DIN 42 973 (kW) and NEC 96 / UL 508 (hp).
Ambient temperature = 40 °C
Ambient temperature = 50 °C
Ambient temperature = 60 °C
200V
230 V
460V
I
e
Order number
460V
575V
I
e
Order number
Pe in hp
Pe in hp
Pe in hp
In A
MLFB
Pe in hp
Pe in hp
In A
MLFB
1
1
3
4.8
3RW3014-1CB.4
-
-
-
-
2
2
5
7.8
3RW3016-1CB.4
-
-
-
-
3
3
7.5
11
3RW3024-1AB.4
7.5
10
11
3RW3024-1AB.5
5
5
10
17.5
3RW3025-1AB.4
10
15
17.5
3RW3025-1AB.5
7.5
7.5
15
25.3
3RW3026-1AB.4
15
20
25.3
3RW3026-1AB.5
7.5
7.5
20
27
3RW3034-1AB.4
20
25
27
3RW3034-1AB.5
10
10
25
34
3RW3035-1AB.4
25
30
34
3RW3035-1AB.5
10
15
30
42
3RW3036-1AB.4
30
40
42
3RW3036-1AB.5
20
20
40
62.1
3RW3044-1AB.4
40
60
62.1
3RW3044-1AB.5
20
25
50
68
3RW3045-1AB.4
50
60
68
3RW3045-1AB.5
30
30
75
99
3RW3046-1AB.4
75
100
99
3RW3046-1AB.5
Table 8-25: 3RW3 motor ratings in acc. with NEMA at 40° C
200V
230 V
460V
I
e
Order number
460V
575V
I
e
Order number
Pe in hp
Pe in hp
Pe in hp
In A
MLFB
Pe in hp
Pe in hp
In A
MLFB
1
1
3
4.8
3RW3014-1CB.4
-
-
-
-
2
2
5
7.8
3RW3016-1CB.4
-
-
-
-
3
3
7.5
11
3RW3024-1AB.4
7.5
10
11
3RW3024-1AB.5
3
3
10
14
3RW3025-1AB.4
10
10
14
3RW3025-1AB.5
5
5
15
21
3RW3026-1AB.4
15
15
21
3RW3026-1AB.5
7.5
7.5
20
27
3RW3034-1AB.4
20
25
27
3RW3034-1AB.5
7.5
10
20
32
3RW3035-1AB.4
20
30
32
3RW3035-1AB.5
10
10
25
38
3RW3036-1AB.4
25
30
38
3RW3036-1AB.5
15
20
40
54
3RW3044-1AB.4
40
50
54
3RW3044-1AB.5
20
20
40
64
3RW3045-1AB.4
40
60
64
3RW3045-1AB.5
25
30
60
85
3RW3046-1AB.4
60
75
85
3RW3046-1AB.5
Table 8-26: 3RW3 motor ratings in acc. with NEMA at 50° C
200 V
230 V
460 V
I
e
Order number
460 V
575 V
I
e
Order number
Pe in hp
Pe in hp
Pe in hp
In A
MLFB
Pe in hp
Pe in hp
In A
MLFB
0.75
0.75
2
4
3RW3014-1CB.4
-
-
-
-
1.5
1.5
3
7
3RW3016-1CB.4
-
-
-
-
2
2
5
9
3RW3024-1AB.4
5
7.5
9
3RW3024-1AB.5
3
3
7.5
12
3RW3025-1AB-4
7.5
10
12
3RW3025-1AB.5
5
5
10
18
3RW3026-1AB.4
10
15
18
3RW3026-1AB.5
5
7.5
15
23
3RW3034-1AB.4
15
20
23
3RW3034-1AB.5
7.5
7.5
20
27
3RW3035-1AB.4
20
25
27
3RW3035-1AB.5
7.5
10
20
32
3RW3036-1AB.4
20
30
32
3RW3036-1AB.5
10
15
30
46
3RW3044-1AB.4
30
40
46
3RW3044-1AB.5
15
20
40
54
3RW3045-1AB.4
40
50
54
3RW3045-1AB.5
20
25
50
72
3RW3046-1AB.4
50
60
72
3RW3046-1AB.5