3RW3 semiconductor motor control unit
SIRIUS System Manual
GWA 4NEB 430 0999-02b
8-7
Star-delta starter
After a delay, the motor windings are switched from a star to a delta config-
uration. The motor current for star starting is only about 1/3 of that required
for delta starting (motor torque, too, is reduced to approximately 1/3 of the
delta torque).
Disadvantages:
• 6 motor cables are necessary
• Switching surges occur (in the current and torque transients)
• The startup cannot be adapted to the system environment
• Installation is relatively complicated and time-consuming
• More space is needed in the cubicle
Figure 8-2: Current and torque curves for star-delta starting