3RP10, 3RP15 solid-state time relays
SIRIUS System Manual
7-26
GWA 4NEB 430 0999-02b
7.7 Technical specifications
Technical specifications in acc. with IEC 61812-1/DIN VDE 0435 Part 2021
Table 7-8: Technical specifications for the time relay
1) If not specified otherwise
2) Maximum making current peak 1 A/100 ms
3) With 3RP15 05-.R: NC contact
−>
I
e
= 1 A
4) Without any welding in acc. with IEC 60 947-5-1.
5) With RP15 05.-BW30/ .AW30/ .RW30 and 3RP15 25-.BW30 voltage-dependent 10 to 250 ms.
6) Minimum on-time with 3RP15 00-. BW30 150 ms until instantaneous contact is switched.
7) Adhere to minimum on-time for problem-free functioning.
Type
3RP10 00
3RP15 05
3RP15 11
3RP15 40
3RP15 60
3RP15 74
3RP15 27
3RP10 20
3RP15 31
3RP15 12
3RP15 76
3RP15 32
3RP15 13
3RP15 33
3RP15 25
3RP15 55
Rated insulation voltage
VAC
300; 500 with 3RP1505-1BT20
Pollution degree 3
Overvoltage category III in acc. with DIN VDE 0110
Excitation operating range
1
)
0.85 to 1.1 x
U
s
with AC; 0.8 to 1.25 x
U
s
with DC
0.95 to 1.05 times the rated frequency
Rated power
W
1
2
2
2
2
2
1
Power input at 230 VAC, 50 Hz
VA
4
6
6
2
2
)
6
6
1
Rated operational currents
I
e
AC-15 at 230 VAC, 50 Hz
A
3
3
)
–
AC-14; DC-13
–
0.01 to 0.6
DC-13 at 24 V
1
–
DC-13 at 48 V
0.45
–
DC-13 at 60 V
0.35
–
DC-13 at 110 V
0.2
–
DC-13 at 230 V
0.1
–
DIAZED fuse
4
)
Performance class
gL/gG
A
4
–
Switching frequency
• Loaded with
I
e
230 VAC
1/h
2500
5000
• Loaded with 3RT10 16 contactor, 230 VAC
1/h
5000
5000
Recovery time
ms
150
5
)
300
150
50
Minimum on-time
ms
35
35
6
)
–
200
7
)
–
Residual current
mA
≤
5
With output not switched through
Voltage drop
V
≤
3.5
Switched through
Short-term current-carrying capa-
city
A
10
(to 10 ms)
Setting accuracy
Typically ±5%
Related to the end of scale value
Repeatability
≤
±1%
Mechanical service life
Operating cycles
30 x 10
6
100 x 10
6
Permissible ambient temperature
In operation
°C
-25 to +60
During storage
°C
-40 to +85
Degree of protection
IP 40 lid
In acc. with EN 60 529
IP 20 terminals
Shock resistance
g/ms
15/11
Half-sine in acc. with IEC 60 068-2-27
Vibration resistance in acc. with IEC 60 068-2-6
Hz/mm 10-55/0.35
EMC tests
IEC 61 000-6-2/EN 50 081-1
In acc. with the basic specification