3RT1/3RH1 contactors
SIRIUS System Manual
GWA 4NEB 430 0999-02b
3-117
1) Corresponds to section from IEC 60 947-4 (VDE 0660 Part 102):
Coordination type "1":
The destruction of the contactor and the overload relay is permissible. The contactor and/or overload relay must be replaced, if necessary.
Coordination type "2":
The overload relay must not be damaged. Contact welding on the contactor is permissible, if it can be easily
separated again from the contactor.
2) Test conditions in acc. with IEC 60 947-4-1.
Unwelded 3RT11 contactors, see Chapter 5 (overload and short-circuit protection only with the 3RV10 circuit breaker).
2) Resistance-heated industrial furnaces and electric heating appliances, etc. (increased current consumption at startup of heating taken into account).
3RT10 3. contactors for switching motors
Contactor
Frame size
Type
S2
3RT10 34
S2
3RT10 35
S2
3RT10 36
Auxiliary circuit
Fuse applications, performance class gL/gG
A
10
10
10
DIAZED type 5SB, NEOZED type 5SE
(unwelded fuse at
I
k
≥
1 kA)
Or miniature circuit breaker with C characteristic
(short-circuit current
I
k
< 400 A)
A
10
10
10
Contactor
Frame size
Type
S2
3RT10 34
S2
3RT10 35
S2
3RT10 36
Drive
Operating range of the magnet coils
AC/DC
0.8 to 1.1 x
U
s
Power input of the magnet coils
(cold coil and at 1.0 x
U
s
)
Standard version
AC operation
Hz
50
50/60
50
50/60
Making capacity
cos
ϕ
Holding power
cos
ϕ
VA
VA
104
127
/113
0.78
0.73/ 0.69
9.7
11.3
/ 9.5
0.42
0.41/ 0.42
145
170
/155
0.79
0.76/
0.72
12.5
15 /
11.8
0.36
0.35/
0.38
For USA and Canada
Hz
50
60
50
60
50
60
Making capacity
cos
ϕ
Holding power
cos
ϕ
VA
VA
90
118
0.76
0.8
11
12
0.38
0.41
160
127
0.82
0.85
13.5
14.2
0.34
0.37
160
127
0.82
0.85
13.5
14.2
0.34
0.37
DC operation
making capacity = holding power
W
13.3
13.3
13.3
Main circuit
Current carrying capacity with alternating current
Utilization category AC-1, switching of resistive
loads
Rated operational currents
I
e
At 40 °C up to 690 V
At 60 °C up to 690 V
A
A
50
45
60
55
55
50
Rated power
of three-phase loads
2
)
cos
ϕ
= 0.95 (at 60 °C)
At 230 V
400 V
500 V
690 V
kW
kW
kW
kW
18
31
39
54
22
38
46
66
20
35
43
60
Minimum conductor cross-section loaded with
I
e
At 40 °C
60 °C
mm
2
mm
2
16
10
16
16
16
10