3RV1 circuit breaker
SIRIUS System Manual
GWA 4NEB 430 0999-02b
2-61
Permissible rating of approved devices for North America,
u s
The circuit breakers in the SIRIUS 3RV1 series are approved for
u
/
s
and can also be used in acc. with UL 508 and C22.2 No.14 with a
contactor as a load feeder. You can use these circuit breakers as a "Manual Motor Starter" for "Group Fusing" or for "Group Installation" or as a
"Combination Motor Controller
Type E
".
3RV1 circuit breaker as a "Manual Motor Starter"
When the circuit breaker is used as a "Manual Motor Starter", it is always with a device for short-circuit protection (upstream short-cir-
cuit protection device). Any fusible link ("group fusing") or circuit breaker ("group installation") can be used as a device for short-circuit
protection. The type and size are selected in acc. with the American NFPA 70 standard, Article 430-53 (c) for adequate protection of
supply lines.
Accreditation was issued under the following file numbers with the listed data:
u
File No. E14705, Product Class NLRV
s
File No. LR12730, Product Class 3211 05
Circuit breaker
Hp rating
Rated current
To 240 VAC
To AC 480 Y/277 V
To AC 600 Y/347 V
For FLA max.
I
n
I
cu
1
)
I
cu
1
)
I
cu
1
)
Type
V
1-phase
3-phase
A
kA
kA
kA
0.11 to 2
50
50
10
3RV10 11
2.5
50
50
10
3RV16 11-0BD10
115
½
-
3.2
50
50
10
200
1½
3
4
50
50
10
Frame size S00
230
2
3
5
50
50
10
460
-
7½
6.3
50
50
10
FLA max. 12 A, 600 V
575/600
-
10
8
50
50
10
NEMA Size 00
10
50
50
10
12
50
50
10
0.11 to 3.2
50
50
30
3RV10 21/3RV11 21
4
50
50
30
3RV13 21
5
50
50
30
115
2
-
6.3
50
50
30
Frame size S0
200
3
7½
8
50
50
30
230
5
7½
10
50
50
30
FLA max. 25 A, 600 V
460
-
15
12.5
50
50
30
NEMA Size 1
575/600
-
20
16
50
50
30
20
50
50
30
22
50
50
30
25
50
50
30
3RV10 31/3RV11 31
11 to 16
50
50
25
3RV13 31
20
50
50
25
115
3
-
25
50
50
25
Frame size S2
200
7½
15
32
50
50
25
230
10
20
40
50
50
25
FLA max. 50 A, 600 V
460
-
40
45
50
50
25
NEMA Size 2
575/600
-
50
50
50
50
25
11 to 16
50
50
30
3RV10 41/3RV10 42
20
50
50
30
3RV11 42
115
10
-
25
50
50
30
3RV13 41/3RV13 42
200
20
30
32
50
50
30
230
20
40
40
50
50
30
Frame size S3
460
-
75
50
50
50
30
575/600
-
100
63
50
50
30
FLA max. 99 A, 600 V
75
50
50
30
NEMA Size 3
90
50
50
30
100 (99)
50
50
30
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) Corresponds to "short circuit breaking capacity" in acc. with UL