3RT1/3RH1 contactors
SIRIUS System Manual
3-120
GWA 4NEB 430 0999-02b
3RT10 4. contactors for switching motors
1) Corresponds to section from IEC 60 947-4 (VDE 0660 Part 102):
Coordination type "1":
The destruction of the contactor and the overload relay is permissible. The contactor and/or overload relay must be replaced, if necessary.
Coordination type "2":
The overload relay must not be damaged. Contact welding on the contactor is permissible, if it can be easily
separated again from the contactor.
2) Test conditions in acc. with IEC 60 947-4-1
Contactor
Frame size
Type
S3
3RT10 4.
Mechanical
life
Basic units
Basic unit with attached auxiliary switch block
Electronically optimized auxiliary switch block
Opera-
ting
cycles
10 mill.
10 mill.
5 mill.
Rated insulation voltage
U
i
(pollution degree 3)
V
1000
Protective separation
between the coil and main contacts
(in acc. with DIN VDE 0106 Part 101 and A1 [Draft 2/89])
V
690
Permissible ambient temperature
For operation
During storage
°C
°C
–25 to +60
–55 to +80
Degree of protection
in acc. with IEC 60 947-1 and DIN 40 050
IP 20 (terminal housing IP 00), actuating system IP 40
Shock resistance
Rectangular impulse
AC and DC operation
g
/ms
6.8/5 and 4/10
Sine pulse
AC and DC operation
g
/ms
10.6/5 and 6.2/10
Short-circuit protection for contactors without overload relay
Short-circuit protection for contactors with overload relay, see Part 4.
Short-circuit protection for fuseless load feeders, see Chapter 5.
Contactor
Frame size
Type
S3
3RT10 44
S3
3RT10 45
S3
3RT10 46
Main circuit
Fuse applications, performance class gL/gG
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE
– In acc. with IEC 60 947-4/DIN EN 60 947-4
(VDE 0660 Part 102)
Coordin. type "1"
1
)
A
250
250
250
Coordin. type "2"
1
)
A
125
160
160
Unwelded
2
)
A
63
100
100
Auxiliary circuit
Fuse applications, performance class gL/gG
A
10
10
10
(unwelded fuse at
I
k
≥
1 kA)
DIAZED type 5SB, NEOZED type 5SE
Or miniature circuit breaker with C characteristic (short-circuit current
I
k
< 400 A)
A
10
10
10
Contactor
Frame size
Type
S3
3RT10 44
S3
3RT10 45
S3
3RT10 46
Drive
Operating range of the magnet coils
AC/DC
0.8 to 1.1 x
U
s
Power input of the magnet coils
(cold coil and at 1.0 x
U
s
)
Standard version
AC operation
Hz
50
50/60
50
50/60
50
50/60
Making capacity
cos
ϕ
Holding power
cos
ϕ
VA
VA
218
247
/211
0.61
0.62/
0.57
21
25
/ 18
0.26
0.27/
0.3
270
298
/274
0.68
0.7 /
0.62
22
27
/ 20
0.27
0.29/
0.31
270
298
/274
0.68
0.7 /
0.62
22
27
/ 20
0.27
0.29/
0.31
For USA and Canada
Hz
50
60
50
60
50
60
Making capacity
cos
ϕ
Holding power
cos
ϕ
VA
VA
218
232
0.61
0.55
21
20
0.26
0.28
270
300
0.68
0.52
22
21
0.27
0.29
270
300
0.68
0.52
22
21
0.27
0.29
DC operation
making capacity = holding power
W
15
15
15