3RT1/3RH1 contactors
SIRIUS System Manual
3-110
GWA 4NEB 430 0999-02b
3 3RT1/3RH1 contactors
3.7 Technical specifications
3RT10 contactors for switching motors
s
and
u
rating data of the contactors
Contactor
Frame size
Type
S00
3RT10 15
S00
3RT10 16
S00
3RT10 17
S0
3RT10 23/24
S0
3RT10 25
S0
3RT10 26
Rated insulation voltage
VAC
600
600
600
600
600
600
Continuous current at 40 °C
Open and enclosed
A
20
20
20
35
35
35
Maximum horsepower ratings
(
s
and
u
approved values)
Rated power
At 200 V hp
1½
2
3
2/3
5
7½
of three-phase induction motors
230 V hp
2
3
3
3/3
5
7½
At 50/60 Hz
460 V hp
3
5
7½
5/7½
10
15
575 V hp
5
7½
10
7½/10
15
20
Short-circuit protection
kA
5
5
5
5
5
5
(contactor or overload relay)
Fuse or circuit breaker to
UL 489
A
A
60
50
60
50
60
50
70
70
70
70
100
100
NEMA/EEMAC ratings
NEMA/EEMAC SIZE
–
–
0
–
–
1
Continuous current
Open
A
–
–
18
–
–
27
Enclosed
A
–
–
18
–
–
27
Rated power
At 200 V hp
–
–
3
–
–
7½
of three-phase induction motors
230 V hp
–
–
3
–
–
7½
At 60 Hz
460 V hp
–
–
5
–
–
10
575 V hp
–
–
5
–
–
10
Overload relay
Type
3RU11 16
3RU11 2
Adjustment range
A
0.11 to 12
1.8 to 25
Contactor
Frame size
Type
S2
3RT10 34
S2
3RT10 35
S2
3RT10 36
S3
3RT10 44
S3
3RT10 45
S3
3RT10 46
Rated insulation voltage
VAC
600
600
600
600
600
600
Continuous current at 40 °C
Open and enclosed
A
45
55
50
90
105
105
Maximum horsepower ratings
(
s
and
u
approved values)
Rated power
At 200V hp
10
10
15
20
25
30
of three-phase induction motors
230 V hp
10
15
15
25
30
30
At 50/60 Hz
460V hp
25
30
40
50
60
75
575V hp
30
40
50
60
75
100
Short-circuit protection
kA
5
5
5
10
10
10
(contactor or overload relay)
Fuse or circuit breaker
to UL 489
A
A
125
125
150
150
200
200
250
250
300
300
350
400
NEMA/EEMAC ratings
NEMA/EEMAC SIZE
–
–
2
–
–
3
Continuous current
Open
A
–
–
45
–
–
90
Enclosed
A
–
–
45
–
–
90
Rated power
At 200V hp
–
–
10
–
–
25
of three-phase induction motors
230 V hp
–
–
15
–
–
30
At 60 Hz
460 V hp
–
–
25
–
–
50
575 V hp
–
–
25
–
–
50
Overload relay
Type
3RU11 3
3RU11 4
Adjustment range
A
5.5 to 50
18 to 100
s
and
u
rating data of the auxiliary contacts
Contactor
Frame size
S00
Screw-type termi-
nal and Cage
Clamp terminal
S0 to S12
Screw-type termi-
nal and Cage
Clamp terminal
Screw-type termi-
nal and Cage
Clamp terminal
Screw-type termi-
nal and Cage
Clamp terminal
Integrated or snap-
on aux. switch block
4-pole snap-on aux.
switch block
1-pole snap-on
aux.switch block
Laterally attachable
aux. switch block
Rated voltage
VAC
600
600
600
600
Switching capacity
A 600, Q 600
A 600, Q 600
A 600, Q 600
A 300, Q 300
Continuous current at 240 VAC
A
10
10
10
10