3RV1 circuit breaker
SIRIUS System Manual
2-64
GWA 4NEB 430 0999-02b
No backup fuse required because it is short circuit-proof up to 100 kA.
1
A backup fuse is only required if the short-circuit current at the installation location is >
I
cu
.
2
10% overvoltage
3
5% overvoltage
Circuit
breaker
Rated
current
I
n
To 240 VAC
2
)
To 400 VAC
2
)/415 V
3
)
To 440 VAC
2
)/460 V
3
) To 500 VAC
2
)/525 V
3
)
To 690 VAC
2
)
I
cu
I
cs
Max.
I
cu
I
cs
Max.
I
cu
I
cs
Max.
I
cu
I
cs
Max.
I
cu
I
cs
Max.
Fuse
Fuse
Fuse
Fuse
Fuse
(gL/gG)
(gL/gG)
(gL/gG)
(gL/gG)
(gL/gG)
Type
A
kA
kA
A
kA
kA
A
kA
kA
A
kA
kA
A
kA
kA
A
3RV1. 41
Frame size S3
40
100
100
50
25
125
1
)
50
20
125
1
)
12
6
100
6
3
63
50
100
100
50
25
125
1
)
50
20
125
1
)
12
6
100
6
3
80
63
100
100
50
25
160
1
)
50
20
160
1
)
12
6
100
6
3
80
75
100
100
50
25
160
1
)
50
20
160
1
)
8
4
125
5
3
100
90
100
100
50
25
160
1
)
50
20
160
1
)
8
4
125
5
3
125
100
100
100
50
25
160
1
)
50
20
160
1
)
8
4
125
5
3
125
3RV1.42
Frame size S3
With increased
switching
capacity
16
100
100
100
50
100
50
30
15
80
12
7
63
20
100
100
100
50
100
50
30
15
80
12
7
63
25
100
100
100
50
100
50
30
15
80
12
7
63
32
100
100
100
50
100
50
22
11
100
12
7
63
40
100
100
100
50
100
50
18
9
160
12
6
80
50
100
100
100
50
100
50
15
7.5
160
10
5
100
63
100
100
100
50
70
50
200
1
)
15
7.5
160
7.5
4
100
75
100
100
100
50
70
50
200
1
)
10
5
160
6
3
125
90
100
100
100
50
70
50
200
1
)
10
5
160
6
3
160
100
100
100
100
50
70
50
200
1
)
10
5
160
6
3
160