3RW3 semiconductor motor control unit
SIRIUS System Manual
GWA 4NEB 430 0999-02b
8-47
Fuse configurations
with SITOR 3NE8
The following table specifies the fuse configuration (coordination type 2) for
3RW30/31 with SITOR fuses 3NE8 (semiconductor protection is provided by
the fuse; line protection and overload protection are provided by the circuit
breaker); max. short-circuit current 50 kA/400 V:
Table 8-19: Fuse configurations (SITOR)
1) Coordination with pure semiconductor protection fuses is not possible;
all-range fuses 3NE1..-0 can be used (see the table above)
2) The selection and setting of the circuit breaker is based on the rated cur-
rent for the motor
3) Note the unit of quantity
If the motor is to be configured to meet UL requirements, the order number
of the fuse must be specified (3NE80..-1).
Order number
Soft starter
Order
number
of the fuse
Rated cur-
rent of the
fuse
Frame
size of
the fuse
Order
number
of the circuit
breaker
2)
Link module
3RW - 3RV
MLFB
MLFB
A
Size
MLFB
MLFB
3)
3RW3014
3NE8003
35
00
3RV1011
3RA1911-1A
3RW3016
3NE8003
35
00
3RV1011
3RA1911-1A
3RW3024/3RW3124
3NE8003
35
00
3RV1021
3RA1921-1A
3RW3025/3RW3125
3NE8003
35
00
3RV1021
3RA1921-1A
3RW3026/3RW3126
--
1)
--
--
--
--
3RW3034
3NE8022
125
00
3RV1031
3RA1931-1A
3RW3035
3NE8024
160
00
3RV1031
3RA1931-1A
3RW3036
3NE8024
160
00
3RV1031
3RA1931-1A
3RW3044
3NE8024
160
00
3RV1041
3RA1941-1A
3RW3045
3NE8024
160
00
3RV1041
3RA1941-1A
3RW3046
3NE8024
160
00
3RV1041
3RA1941-1A