Functions
3.6 Motor protection
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
47
Response to overload temperature sensor
You use this parameter to specify how the motor starter is to respond in an overload
temperature sensor situation:
●
Tripping without restart (AUTO RESET = off)
●
Tripping with restart (AUTO RESET = on)
WARNING
Motor restarts automatically if AUTO RESET is on.
Can Cause Death, Serious Injury, or Property Damage
The motor starter restarts automatically after the recovery time if a start command is
present (autoreset).
Make sure that you take appropriate measures to exclude the risk of hazardous conditions.
●
Warning
Temperature sensor monitoring
Temperature sensor monitoring is activated when a PTC type A temperature sensor is
parameterized. It is then automatically deactivated if thermoclick is parameterized.
This device parameter monitors the temperature sensor cable for interruptions (wire break)
and short circuits. The motor is shut down (depending on the parameterization).
Settings
Device parameter
Default setting
Setting range
Response to overload temperature sensor
Tripping without
restart
•
Tripping without restart
•
Tripping with restart
•
Warning
Temperature sensor
Deactivated
•
Deactivated
•
Themoclick
•
PTC type A
Temperature sensor monitoring
Yes
•
Yes
•
No
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......