Functions
3.15 Factory settings
M200D PROFIBUS/PROFINET
76
Manual, 08/2014, A5E01577426A/RS-AA/004
Test steps
The self-test comprises 3 test steps. The test steps are followed in dependence of the signal
duration of the test command:
Test step
Signal
duration
Test scope
Explanations
1
< 2 s
LED test
All LEDs are switched on for 2 seconds!
•
User check, no message bit
2
2 to 5 s
Hardware test The hardware of the motor starter is tested;
Current measurement indicated by the "DEVICE" LED:
•
Current flowing: flashing red
•
Current not flowing: flickering red
•
User check, no message bit
3
1)
> 5 s
Trip
Switching elements are switched off.
1)
This test step is only executed in manual mode
Self-test error
If an error occurs, the "DEVICE" LED lights up red. The error can only be acknowledged by
switching the device off and then on again. If the error is still present, the self-test will return
an error again when the device is switched on. In this case, the motor starter must be
replaced.
Messages and actions
Messages
Actions
Self-test active
-
Self-test ok
-
Self-test error
-
Note
Specific device components are monitored continuously (internally) by the motor starter and
the results signaled with the self-test messages. The message "Self-test error" can also
appear in the case of an internal monitoring fault without the self-test having been activated.
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......