Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
199
Object No.
Trips - Messages
355
Process image error
365
Invalid parameter value
381
Self-test error (= device error)
1406
Cold start tripping
1201
Blocking protection has responded at startup
1202
Blocking protection has responded during operation
A.1.8
DS75 logbook - Read events
Byte
Data type
Meaning
Range of values
Increment
Entry 1 (= latest entry)
0 ... 3
Unsigned 32
Operating hours - device
0 ... 4 294 967 295
1 s
4 ... 5
Unsigned 16
Object number
± 0 ... 32767
1
Entry 2
6 ... 9
Unsigned 32
Operating hours - device
0 ... 4 294 967 295
1 s
10 ... 11
Unsigned 16
Object number
± 0 ... 32767
1
...
...
Entry 21
120 ... 123 Unsigned 32
Operating hours - device
0 ... 4 294 967 295
1 s
124 ... 125 Unsigned 16
Object number
± 0 ... 32767
1
The data record call "Logbook" returns the operating hour of the event that has occurred and
an associated object number for each entry. This data set can accommodate 21 entries.
When all locations have been overwritten, the oldest entry is overwritten again.
Note
The latest entry is entered at the first location of the data set. The remaining entries are
moved one entry up.
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......