Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
127
5.2.2
Parameter overview
More information on the individual parameters can be found in Chapter Functions (Page 25).
The table below provides an overview of all parameters of the
M200D PROFIBUS/PROFINET motor starter.
Device parameter
Default setting
Setting range
Basic functions / parameters (Page 27)
Rated operating
current
•
In the motor starter:
maximum value
•
In GSD/Motor Starter ES:
minimum value
•
0.15 A to 2.0 A
•
1.5 A to 9.0 A
1)
•
1.5 A to 12.0 A
Increment: 10 mA
Load type
3-phase
•
3-phase
•
1-phase
Protection against
voltage failure
Yes
•
Yes
•
No
Response to no
switching element
supply voltage
Group fault
•
Group fault
•
Group fault only after ON command
•
Group warning
Fieldbus interface (Page 31)
Response to
CPU/master STOP
Switch substitute value
•
Switch substitute value
•
Retain last value
Substitute value
0
8 bits (0 or 1)
Group diagnostics
block
•
block
•
enable
Motor control (Page 33)
Lock-out time
0
0 to 60 s increment: 1 s
Starting time (x 0.25 s) 5 s
0 to 30 s increment: 0.25 s
Run-down time
0
0 to 30 s increment: 0.25 s
Startup mode
direct
•
direct
•
Voltage ramp
•
Current limiting
•
Voltage ramp + current limiting
Run-down type
Run-down without load
•
Run-down without load
•
Voltage ramp
Starting voltage
40 %
20 % to 100 % increment: 5 %
Stopping voltage
40 %
20 % to 90 % increment: 5 %
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......