Mounting / connection
4.2 Connection
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
113
Requirements
●
The communication module is mounted on the motor starter module as shown in Chapter
Installing the communication module (Page 99)
●
You have set the PROFIBUS DP address on the DIP switch according to your
configuration. Further information: Setting the PROFIBUS DP address and terminating
Required tools
●
Screwdriver, (PZ 2; 2 Nm)
●
Stripping tool for wiring the M12 and 7/8" cable connectors, if you are fabricating your
own cables.
Required accessories
●
Prefabricated cable with M12 and 7/8" cable connectors The cables are available in
different lengths.
●
If you are fabricating your own cable:
–
M12: 2-core, shielded bus cable, and b-coded M12 cable connectors
–
7/8": 4-core cable with 7/8" cable connectors
Pin assignment of the M12 and 7/8" cable connectors
PROFIBUS connection (M12)
Coding (M12 B-coded)
Pin (infeed)
Socket (routing)
Pin
Assignment
M12-B
1
Power supply plus (5 V)
2
Data line A
3
Data reference potential (0 V)
4
Data line B
5
Functional ground (FE)
Note
The voltage must not be looped through to the next plug connector using a cable.
Note
The functional ground is to be connected via the M12 thread (because it has a larger surface
area than terminal 5).
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......