Functions
3.10 Communication over PROFIBUS/PROFINET
M200D PROFIBUS/PROFINET
70
Manual, 08/2014, A5E01577426A/RS-AA/004
3.10.4
Message output
Message
Meaning
General messages
Ready (automatic)
Device can be activated via the BUS (e.g. PLC).
Group fault
At least one fault is set.
Group warning
At least one warning is present.
Group prewarning
At least one pre-warning is present.
Process image error
The process image of the outputs contains an illegal
bit combination, e.g. motor CW and motor CCW set
simultaneously.
Fieldbus interface
Bus error
Fieldbus interface threshold monitoring expired.
CPU/Master STOP
PLC program is no longer processed.
Acknowledgment
Trip reset executed
Trip reset accepted; that is, error/fault has been
acknowledged.
Trip reset not possible
Fault could not be acknowledged since the cause of
the tripping is still pending.
Mode monitoring
Automatic mode
Automatic (PLC controls)
Manual bus mode
Manual mode via fieldbus (HMI controls)
Manual local mode
Manual local mode:
•
Manual mode via Motor Starter ES
•
HMI controls
•
Input controls
Connection abort in manual mode
During manual mode, the relevant communication
connection was interrupted for more than 5 seconds.
Parameter assignment
Parameter assignment active
Yes/No
Invalid parameter value
1)
Parameter not correct
Parameters cannot be changed in ON state
1)
Attempt to change parameters while motor is is
running not permissible.
Parameter number error
1)
Specifies the first unaccepted parameter (object
number of the parameter).
Parameters disabled CPU/master active
Motor starter ignores parameters from the PLC but
informs the PLC that the parameters are in order.
No external startup parameters received
No new parameters have been received from the
PLC after Power ON or restart of the motor starter.
Statistical data
Maximum pointer deleted
1)
Preventive diagnosis statistical data has been reset.
1)
Message bits that can be deleted with trip reset
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......