Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
126
Manual, 08/2014, A5E01577426A/RS-AA/004
5.2
Parameterize
5.2.1
Parameter dependencies in the GSD/GSDML
Note
When parameterizing with the GSD/GSDML file, values can be selected that are mutually
dependent and are not permissible in combination! The relevant parameter is reported as
"Invalid parameter value" in data set 92!
The following table shows which parameters are mutually dependent and how they must be
set:
Dependent parameters
Setting
Current limit values
Lower current limit < upper current limit
Temperature sensor deactivated
CLASS OFF
With CLASS OFF: "Temperature sensor deactivated" not possible
with "Temperature sensor deactivated": "CLASS OFF" not
possible
Startup mode
Max. rated operating current I
e
(only for sDSSte, sRSSte with I
e, max
= 12 A)
with direct startup mode: I
e,max
= 9.0 A
Startup mode
Trip class CLASS
(only for sDSSte, sRSSte)
with direct startup mode: Restriction to CLASS 5 (10a), 10 and
CLASS OFF
Maintenance timer warning limits Maintenance timer warning limit 1 < maintenance timer warning
limit 2
Input n signal
Input n level
Input n action
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......