Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
213
Object
No.
Byte.Bit
Parameters / content
Range of values
Increment
Default
setting
Relevant for
163
96
Output 1 action
[00]: No action
[01]: Control source PIO DO 1.0
[02]: Control source PIO DO 1.1
[03]: Control source PIO DO 0.2
[06]: Control source input 1
[07]: Control source input 2
[08]: Control source input 3
[09]: Control source input 4
[10]: Run-up
[11]: Operation/shunting
[12]: Coasting down
[13]: On time motor (RUN)
[14]: Control command motor
(ON)
[17]: Brake output
[18]: Device ON
[30]: Group prewarning
[31]: Group warning
[32]: Group fault
[33]: Bus error
[34]: Device error
[35]: Maintenance required
[36]: Maintenance requested
[38]: Ready for motor ON
—
[01]
All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
sDSS../sRSS..
sDSS../sRSS..
sDSS../sRSS..
All starters
All starters
With BO only
All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
164
97
Output 2 action
[00]: No action
[01]: Control source PIO DO 1.0
[02]: Control source PIO DO 1.1
[03]: …[38]: See byte 96
—
[02]
All starters
All starters
All starters
230
137.0 ... 3 Connector monitoring
[0]: Deactivated
[1]: Line side
—
[0]
All starters
231
137.4 ... 7 Response when
connector removed
[0]: Group fault
[1]: Group fault only after ON
command
[2]: Group warning
—
[0]
All starters
1)
BO: Brake output
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......