Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
128
Manual, 08/2014, A5E01577426A/RS-AA/004
Device parameter
Default setting
Setting range
Current limit value
(x 3.125%)
•
600% (Ie
≤
9 A)
•
550% (Ie
≤
9 A)
•
Ie
≤
9 A: 125 % ... 600 %
•
Ie > 9 A: 125 % ... 550 %
Increment: 3.125 %
Brake release delay on
starting
0 s
- 2.5 to + 2.5 s
Increment: 0.01 s
Brake holding time on
stopping
0 s
0 to 25 s
Increment: 0.01 s
Motor protection (Page 41)
Response to overload -
thermal motor model
Tripping without restart
•
Tripping without restart
•
Tripping with restart
•
Warning
Trip class
(DSte / RSte, sDSSTe,
sRSSte in startup
mode ≠ direct)
CLASS 10
•
CLASS 5 (10a),
•
CLASS 10
•
CLASS 15,
•
CLASS 20
•
CLASS OFF
Trip class
(sDSSte / sRSSte in
startup mode = direct)
•
CLASS 10
in startup mode = direct
•
CLASS 5 (10a)
in startup mode ≠ direct
•
CLASS 5 (10a),
•
CLASS 10
•
CLASS OFF
Recovery time
90 s
60 to 1800 s
Increment: 30 s
Prewarning limit motor
heating
0% (= deactivated)
0 ... 95 %
Increment: 5 %
Prewarning limit -
remaining time for
tripping
0 s (= deactivated)
0 to 500 s
Increment: 1 s
Idle time
0 s (= deactivated)
0 to 255 s increment: 1 s
Response to overload
temperature sensor
Tripping without restart
•
Tripping without restart
•
Tripping with restart
•
Warning
Temperature sensor
Deactivated
•
Deactivated
•
Themoclick
•
PTC type A
Temperature sensor
monitoring
Yes
•
Yes
•
No
Response to residual
current detection
Trip
•
Warning
•
Trip
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......