Functions
3.7 System monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
61
Settings
Device parameter
Default setting
Setting range
Output level 1
Not inverted
•
Not inverted
•
Inverted
Output level 2
Output 1 signal
Continuous signal
•
Continuous signal
•
Flashing
Output 2 signal
Output 1 action
Control source
PIO DO 1.0
Triggering by means of external control source
•
Control source PIO DO 1.0
(output 1)
•
Control source PIO DO 1.1
(output 2)
•
Control source PIO DO 0.2
1)
(brake output)
•
Control source input 1
•
Control source input 2
•
Control source input 3
•
Control source input 4
Actuation by motor starter
•
Run-up
2)
•
Operation/shunting
2)
•
Coasting down
2)
•
On time motor (RUN)
•
Control command motor ON
•
Brake output
•
Device ON
Actuation by messages from the motor starter
•
Group prewarning
•
Group warning
•
Group fault
•
Bus error
•
Device error
•
Maintenance required
•
Maintenance requested
•
Ready for motor ON
Output 2 action
Control source
PIO DO 1.1
1) Brake output only on starters with BO
2) Run-up, operation/shunting, coasting down only on soft starters.
Messages and actions
Message
Action
Output 1 active
The output is controlled
Output overloaded
Tripping (acknowledgment via trip reset)
Output BO (brake output) active
The brake output is controlled
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......