Diagnostics
7.4 Diagnostics with STEP 7 on PROFIBUS DP
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
159
Fault types
The diagnostics message is signaled on channel 0.
Fault type
Error text
Meaning / cause
Delete/acknowledge message bit
1
dec
00001
B
Short-circuit
•
Temperature sensor - short circuit
•
Circuit breaker tripped
Message bit is automatically deleted when
the cause of the fault has been removed
and acknowledged with "trip reset"
4
dec
00100
B
Overload
•
Temperature sensor - overload
•
Thermal motor model - overload
Message bit is updated continually
5
dec
00101
B
Overtemperature
•
Overload power semiconductor
•
Switching element overload
Message bit is automatically deleted when
the cause of the fault has been removed
and acknowledged with "trip reset"
6
dec
00110
B
Wire break
•
Temperature sensor wire break
Message bit is updated continually
7
dec
00111
B
Upper limit
exceeded
•
I
e
upper limit violation
8
dec
01000
B
Lower limit
undershot
•
I
e
lower limit violation
9
dec
01001
B
Error
•
Internal error/device error
•
Self-test error
•
Switching element defective
•
Switching element short-circuited
Message bit can be deleted when the cause
of the fault has been removed by
•
Switching the supply voltage
(DC24 V-NS) on/off
•
"Restart" command if possible
16
dec
10000
B
Parameter
assignment error
•
Invalid parameter value
•
Parameters cannot be changed in
ON state
Message bit is always deleted when
acknowledged with "trip reset"
17
dec
10001
B
No encoder or
load voltage
•
Electronics supply voltage too low
(< 18 V)
•
No contact block supply voltage
•
No supply voltage
•
Connector disconnected on line
side
Message bit is deleted when the cause of
the trip has been removed or automatically
acknowledged.
24
dec
11000
B
Actuator
disconnection
•
Overload tripping
•
Residual current tripping
•
Asymmetry tripping
•
Circuit breaker tripped
•
I
e
limit tripping
•
Cold start tripping
•
Tripping due to motor blocking
Message bit is always deleted when
acknowledged with "trip reset".
Additional acknowledgment in combination
with another fault
26
dec
11010
B
External error
•
Input tripping
•
Input tripping - end position
(CW / CCW)
•
Quick stop active
•
Sensor supply overload
•
Process image error
•
Output overloaded
Message bit is always deleted when
acknowledged with "trip reset".
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......