Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
192
Manual, 08/2014, A5E01577426A/RS-AA/004
Error codes
The following error codes are generated by the motor starter:
Error codes byte Error messages
Cause
high
Low
00
H
00
H
No error
—
Communication interface
80
H
A0
H
Negative acknowledgment in the case of
"Read data set"
Data set write-only
80
H
A1
H
Negative acknowledgment in the case of
"Write data set"
Data set read-only
80
H
A2
H
Protocol error
•
Layer 2 (fieldbus)
•
Device interface
•
Incorrect coordination
80
H
A9
H
This function is not supported
DPV1 service does not support
Read/write data set
Access to technology
80
H
B0
H
Unknown data set number (DS No)
DS No. not known in motor starter
80
H
B1
H
Incorrect data set length when writing
DS length and specified DS length
different
80
H
B2
H
Incorrect slot number
Slot not 1 or 4
80
H
B6
H
Communication partner has rejected data
transfer
•
Incorrect operating mode
(automatic, manual bus, manual
local)
•
Data set is read-only
•
Parameters cannot be changed
in ON state
80
H
B8
H
Invalid parameter
Invalid parameter value
Device resources
80
H
C2
H
Temporary lack of resources in the device
•
No free receive buffer
•
The data set is currently being
updated
•
The dataset request is currently
active on another interface.
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......