Functions
3.3 Basic functions / parameters
M200D PROFIBUS/PROFINET
28
Manual, 08/2014, A5E01577426A/RS-AA/004
Instructions
●
In the motor starter, the rated operating current is preset at the factory to the maximum
value. (For testing at startup without fieldbus and without previous parameterization)
●
In the GSD and the "Motor Starter ES" software, the rated operating current is preset to
the minimum value for safety reasons. You must therefore parameterize this value when
you configure the system Otherwise the motor starter would trip when it starts for the first
time due to overloading.
●
The rated operating current depends on the "startup mode" parameter on motor starters
with soft starter function. If the startup mode is set as "direct", the choice of rated
operating current is restricted to 9 A.
Settings
Device parameter
Default setting
Setting range
Rated operating current
•
In the motor starter: Maximum value
•
In GSD/Motor Starter ES: Minimum value
•
0.15 A to 2.0 A
•
1.5 A to 9.0 A
1)
•
1.5 A to 12.0 A
Increment: 10 mA
1)
On soft starters (sDSSte, sRSSte) in the startup mode "direct"
Note
The setting range depends on the device type!
Summary of Contents for SIRIUS M200D
Page 2: ......
Page 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Page 233: ......