Connection
6
6.1
Connection requirements
In this section it is described how the components of SIMOTION P320-4 are connected and
the elements for communication prepared.
During the installation of SIMOTION modules, you must pay attention to the electrical
configuration design.
You obtain information on wiring and networking a complete SIMOTION system.
Requirement
The SIMOTION P320-4 is already installed in a cabinet or in a controller housing.
Open equipment
These modules are open equipment. Therefore, only install modules in housings, cabinets, or
in electrical equipment rooms that can only be entered or accessed with a key or tool. Only
instructed or authorized personnel have access.
Observe the following points during installation:
● The device may only be connected to 24 VDC power supplies that meet the requirements
in accordance with SELV. The cable cross-section must be chosen large enough to ensure
that no damage can result from cable overheating in the event of a short-circuit in the
SIMOTION P320‑4.
● Protect the device against dust, moisture, heat and severe vibration.
● Do not subject the SIMOTION P320-4 to direct sunlight.
● Install the device in such a way that it cannot present a hazard (e.g. by toppling).
● Ensure that the clearance to other components or the sides of cabinets is at least 50 mm
above and 100 mm below the device.
SIMOTION P320-4 E / P320-4 S
Commissioning and Hardware Installation Manual, 11/2016
99