Installation and commissioning
4.1 Installation guide
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
63
Dimensions for installation of the components
Table 4- 1
Dimensions for installation of the SINAUT DNP3 components
Module
Module
width
Module
height
Max. depth
Installation
on
Communications module
TIM 3V-IE DNP3
40 mm
125 mm
120 mm or 150 mm with
open front panel
S7 rail
Communications module
TIM 4R-IE DNP3
80 mm
125 mm
120 mm or 180 mm with
open front panel
S7 rail
4.1.6
Permitted ambient temperatures with horizontal and vertical installation
Horizontal and vertical installation
You can operate the DNP3 components both in horizontally and in vertically installed racks.
Permitted ambient temperature
The DNP3 components can be operated in the same temperature range specified for the S7-
300.
Table 4- 2
Permitted ambient temperatures for the SINAUT TIM modules
Installation position
Permitted ambient temperature (operation)
Horizontally installed rack
0 to 60 °C
Vertically installed rack
0 to 40 °C