The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
176
System Manual, 12/2015, C79000-G8976-C253-04
project. The parameter area for the destination subscriber-specific parameters is opened and
the parameters are set for every configured destination subscriber.
The following destination subscriber-specific parameters are available:
Parameters of the DNP3 master station
Name:
DNP3 implementation level
Range of val-
ues:
1 ... 5
Default:
3
Explanation:
With the SINAUT configuration software, you can specify the DNP3 imple-
mentation level for each configured DNP3 master station (subscriber type:
other station). Specify the highest conformity level supported by the DNP3
master station.
Values can be assigned in the range from 1 to 5. Based on this information,
the TIM firmware selects the suitable standard variations of the process
data for this master station.
Level 5 that is not specified in the standard corresponds to implementation
level 4 and additionally includes the support of the following objects / data
types (object group/variation):
•
Frozen counter with time of day in 16-bit format (21/6)
•
Counter event with time of day in 16-bit format (22/6)
•
Analog input, floating point, 32-bit format (30/5)
•
Analog input event, floating point with time, 32-bit format (32/7)
•
Analog output status, floating point, 32-bit format (40/3)
•
Analog output, floating point, 32-bit format (41/3)
Name:
Time stamp
Default:
Function activated
Explanation: When using DNP3, the parameter is always activated. This cannot be deac-
tivated.
The parameter assignment is only practical if the DNP3 master station was
selected as the destination subscriber.
Data read by the local CPU is given a time stamp before it is sent to the des-
tination subscriber.
Copying parameters to other destination subscribers
Once the destination subscriber-specific parameters have been set for a destination
subscriber, they can be transferred to other destination subscribers that require the same
parameters. Follow the steps outlined below:
1.
Select a destination subscriber for which you have already set the parameters in the list
box.
2.
Select "Copy" in the shortcut menu (right mouse button).
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...