Installation and commissioning
4
4.1
Installation guide
4.1.1
Installation of a DNP3 TIM in an S7-300
Installation in a rack
With standard and compact CPU modules, the TIM can be inserted into any of the racks 0 to
3 but only in expansion racks 1 to 3 if these racks are connected to the CPU over the IM
360/IM 361 interface modules.
With the C7 control systems, the TIM can be inserted in any of the expansion racks 1 to 3.
These are connected to the C7 device over IM 360/IM 361 interface modules (the IM 360 is
already integrated in the C7 device). With the C7-635 and C7-636 devices, this is also
possible without the IM 361 if no more than four modules including the TIM are connected
externally.
For all S7-300 racks the following applies: All slots designed for SM, FM or CP can also be
used for the TIM.
A bus module connector ships with every TIM. The TIM is connected to the module to its left
by the bus module connector.
Note
In all of the sample configurations of the S7-300, it is assumed that a 24 V power supply is
available for the CPU, the TIMs and the other modules.
Note
Direct connection of a TIM 3V-IE DNP3 to the PROFINET interface of an S7-300-CPU is not
possible!
4.1.2
Configuration of an S7-300 with a DNP3 TIM
Note
A maximum of one TIM can be installed in an S7-300.
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...