The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
180
System Manual, 12/2015, C79000-G8976-C253-04
Data object
Object type and function
Number of
indexes
occupied
DNP3 object group [vari-
ation]
(S7 data type)
DNP3 level *
Use in stations
type **
Setpoint and parameter objects
Set01W_S
Setpoint object for send direc-
tion
Send 1 setpoint (16 bits), object
with 3 channels:
•
"LocalOperation"
- not used -
•
"ReturnedSetpoint"
Function: Mirrored back
setpoint
Channel type: Data receive
1
•
40 [2] (WORD) ***
•
42 [4] (WORD) ***
•
1 ... 5
•
4 ... 5
M
•
"SetpointInput"
Function: Setpoint input
Channel type: Setpoint
send
1
•
41 [2] (WORD) ****
•
1 ... 5
Set01W_R
Setpoint object for receive
direction
Receive 1 setpoint (16 bits),
object with 3 channels:
•
"Local"
- not used -
•
"LocalSetpointInput"
Function: Local setpoint
Channel type: Data send
1
•
40 [2] (WORD) ***
•
42 [4] (WORD) ***
•
1 ... 5
•
4 ... 5
S
•
"SetpointOutput"
Function: Setpoint output
Channel type: Setpoint re-
ceive
1
•
41 [2] (WORD)
•
1 ... 5
Par12D_S
Parameter object for send
direction
Send max. 12 double words
with parameters or setpoints,
object with 3 channels:
•
"LocalOperation"
- not used -
•
"ReturnedParameter"
Function: Returned parame-
ter
Channel type: Data receive
1 ... 12
•
40 [1] (DINT) ***
•
42 [3] (DINT) ***
•
1 ... 5
•
4 ... 5
M
•
"ParameterInput"
Function: Parameter input
Channel type: Setpoint
send
1 ... 12
•
41 [1] (DINT) ****
•
1 ... 5
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...