The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
224
System Manual, 12/2015, C79000-G8976-C253-04
If the serial interface is set to the standard RS-485, up to 8 MODBUS slaves can be
connected and monitored (1 slave with RS-232).
Name:
Gateway number
Explanation: Internal partner number of TD7onTIM, cannot be set.
Note on the gateway number
In the subscriber management, if a TIM is selected with TD7onTIM with the
system object “ModbusGateway“, in the object list in the column “Partner
no.” with the Modbus objects, the gateway number is displayed preceded by
“G”.
Name:
S7 CPU status output byte
Memory area: The following options are available:
•
DB: Data block
•
Memory bit: Memory bit area
•
Output: Process output image (PIQ)
DB No.:
Specifies the DB number in the CPU if the data block memory area (DB) was
selected
Address
[byte]:
Input box for the byte number in the selected memory area
Name:
MODBUS slaves
Explanation: In the 8 input boxes, the MODBUS slaves to be monitored are assigned to
the 8 status bits of the output byte. The MODBUS address is specified for
each MODBUS slave.
Bit status:
Status = 0: Problem on partner or bit not assigned
Status = 1: Partner OK
ModbusGateway
The "ModbusGateway" system object is used to activate the MODBUS protocol for a serial
interface of the TIM and to configure the connection to the MODBUS slaves.
"Gateway property" box
Name:
Connection to TIM interface
Explanation: Specifying the serial interface of the TIM
Selection for TIM 4R-IE DNP3:
•
WAN 1 = interface X1
•
WAN 2 = interface X2
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...