Configuration in STEP 7
5.9 Configuring time-of-day synchronization
TIM DNP3
138
System Manual, 12/2015, C79000-G8976-C253-04
5.9.4
Synchronization of the TIM time of day by the CPU
Apart from the option of synchronizing the TIM by a master station or using NTP, the TIM
can also be synchronized by its local CPU.
Please note: You require an Ethernet CP in the 400 station.
Follow the steps described below when configuring in STEP 7.
Time-of-day synchronization of the TIM by the 300 CPU
1.
In the properties dialog of the CPU, open the "Diagnostics / Clock" tab.
2.
In the "Clock" box, select the option "As master" in the "On PLC" drop-down list and
select the time interval.
3.
Close the properties dialog of the CPU.
4.
Open the properties dialog of the TIM with the "Time Service" tab.
5.
Select the backplane bus and set the synchronization cycle to the same setting as
configured on the CPU.
6.
Close the dialog and save.
Time-of-day synchronization of the TIM by the 400 CPU
1.
In the properties dialog of the CPU, open the "Diagnostics / Clock" tab.
2.
In the "Clock" box, select the option "As master" in the "On PLC" drop-down list and
select the time interval.
3.
Close the properties dialog of the CPU.
4.
Open the properties dialog of the Ethernet CP and enable the "Enable time-of-day
synchronization" option in the "Options" tab.
5.
Close the properties dialog of the CP.
6.
Open the properties dialog of the TIM with the "Time Service" tab.
7.
Select the backplane bus and set the synchronization cycle to the same setting as
configured on the CPU.
8.
Close the dialog and save.
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...