Data object
Object type and function
Number of
indexes
occupied
DNP3 object group [vari-
ation]
(S7 data type)
DNP3 level *
Use in stations
type **
Par12D_R
Parameter object for receive
direction
Receive max. 12 double words
with parameters or setpoints,
object with 3 channels:
•
"Local"
- not used -
•
"LocalParameterInput"
Function: Local parameters
Channel type: Data send
1 ... 12
•
40 [1] (DINT) ***
•
42 [3] (DINT) ***
•
1 ... 5
•
4 ... 5
S
•
"ParameterOutput"
Function: Parameter output
Channel type: Setpoint re-
ceive
1 ... 12
•
41 [1] (DINT)
•
1 ... 5
Universal data objects
Dat12D_S
Data object for send direction
Send max. 12 double words (at
least 1 double word) with any
information
1 ... 12
•
30 [1] (DINT)
•
30 [5] (REAL)
•
32 [1] (DINT)
•
32 [3] (DINT)
•
32 [7] (REAL)
•
41 [1] (DINT)
•
41 [3] (REAL)
•
1 ... 5
•
5
•
1 ... 3
•
4 ... 5
•
5
•
1 ... 5
•
5
•
S
•
S
•
S
•
S
•
S
•
M
•
M
2 ... 24
•
30 [2] (INT, WORD)
•
32 [2] (INT, WORD)
•
32 [4] (INT, WORD)
•
41 [2] (INT, WORD)
•
1 ... 5
•
1 ... 3
•
4 ... 5
•
1 ... 5
•
S
•
S
•
S
•
M
4 ... 48
•
30 [2] (BYTE)
•
32 [2] (BYTE)
•
32 [4] (BYTE)
•
41 [2] (BYTE)
•
110 [1..255] (CHAR)
•
111 [1..255] (CHAR)
•
1 ... 5
•
1 ... 3
•
4 ... 5
•
1 ... 5
•
1 ... 5
•
1 ... 5
•
S
•
S
•
S
•
M
•
M / S
•
S
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...