Uses and properties of the TIM
1.10 Configuration limits
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
29
Table 1- 2
Overview of the connection resources
TIM type
Subscriber type /
interface configura-
tion
Max. number of
connections per
TIM in total
Interface
Network type
Max. number of
connections per
interface
TIM 4R-IE DNP3
Master station
128 *
Ethernet 1
TCP
64
Ethernet 2
TCP
64
RS232 no. 1
Dedicated line
32
Dial-up network
32
RS232 no. 2
Dedicated line
32
Dial-up network
32
Station
32
Ethernet 1
TCP
16
Ethernet 2
TCP
16
RS232 no. 1
Dedicated line
16
Dial-up network
16
RS232 no. 2
Dedicated line
16
Dial-up network
16
TIM 3V-IE DNP3
Master station /
node station
8
Ethernet
TCP
8
RS232
Dedicated line
8
Dial-up network
8
Station
8
Ethernet
TCP
8
RS232
Dedicated line
8
Dial-up network
8
* The total number of 128 also applies to the TIM 4R IE DNP3 as a node station. The maximum number per interface is
obtained from the information in the "Master station" or "Station" rows.
Number of communications objects per TIM
The maximum number of communications objects for DNP3 communication per TIM is 100.
Size of the message memory for events
●
TIM 3V-IE DNP3: 64 000 events
●
TIM 4R-IE DNP3: 200 000 events
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...