The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
202
System Manual, 12/2015, C79000-G8976-C253-04
Input / output address
Data transferred from TD7onTIM to a communications partner is first read from the work
memory of the CPU. For each send channel, the source address (
input address
) must be
specified in the relevant memory area of work memory on the local CPU module from which
the data will be read.
Name:
Input address
Memory area: The following options are available for the source or destination address:
•
DB: Data block
•
Memory bit: Memory bit area
•
For sending channels:
Input: Process input image (PII)
•
For receiving channels:
Output: Process output image (PIQ)
Only the specified address areas can be read or written by TD7onTIM. Data
from other areas, for example analog values acquired via peripheral input
words (PIW) or output via peripheral output words (PQW) must be mapped
to the bit memory or data block area by the user program.
Data type:
Apart from the objects Dat12D_S, Dat12D_R, Par12D_S, Part12D_R, the
box shows the default data type for the particular channel:
•
Binary send/receive: BYTE
•
Analog send/receive: WORD
•
Mean value send/receive: WORD
•
Counted value send: WORD
•
Counted value receive: DWORD
•
Command send/receive: BYTE
•
DNP command received / DNP command return message: BOOL
•
Send/receive data:
–
Bin08X_S/Bin08X_R: In each case 1 status bit of the byte
–
Dat12D_S/Dat12D_R: BYTE, CHAR, WORD, DWORD, INT, DINT,
REAL
•
Setpoint send/receive
–
Object Set01W_S/Set01W_R: WORD
–
Object Par12D_S/Par12D_R: BYTE, CHAR, WORD, DWORD, INT,
DINT, REAL
Number:
Amount of data included in the array (maximum 12 double words or 48
bytes). The parameter is only active for channels that can be configured with
a variable length. The parameter is available for the following channel/object
types and is explained further below with the specific channel parameters:
•
Data send / Dat12D_S
•
Data receive / Dat12D_R
•
Setpoint send / Par12D_S
•
Setpoint receive / Par12D_R
Summary of Contents for SIMATIC TIM 3V-IE DNP3
Page 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Page 312: ......
Page 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Page 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...