Installation Guidelines
S5-115F Manual
3.2.6
Distributed Configurations
A central controller connected to expansion units installed over a maximum distance of 600 m
(approx. 2000 ft.) makes up a distributed configuration. A distributed configuration is described
on the pages that follow.
Please note the following:
•
Each ER 701-2 expansion rack, or ER 701-3 in a distributed configuration, requires a PS 951
power supply module and an IM 306 interface module for addressing input/output modules.
•
Please note Section 3.4.4!
•
If you use digital input modules on the ER 701-2 or ER 701-3, it is recommended that these be
modules with revision level ”2” (or higher).
Table 3-1. Technical Specifications for Distributed
Configuration Interface Modules
IM 304
8
600 m
1.2 A
0.85 A
Maximum number of EUs that
can be connected
Max. total cable length
Current consumptionat 5 V
IM 314