S5-115F Manual
Rules Governing the Use of the S5-115F
16
32
ON
2
Binary weights of the address bits
1
2
4
6
7
1
5
3
128 64
32
16
8
4
2
The address is equal to the sum of the
weights set by the individual code
switches, e.g.
2+4+8+32=46
Figure 10-37. Setting a DIP Switch
The module is then addressed as follows:
Channel No.
Address
0
46.0
1
46.1
7
8
9
46.7
47.0
47.1
15
47.7
2
3
4
46.2
46.3
46.4
5
6
46.5
46.6
11
12
47.3
47.4
10
47.2
13
14
47.5
47.6
Note
COM 115F CONFIGURE checks the inputs for duplication of addresses, but it does not
check for module address overlap or initial addresses. It can therefore happen that the
address named in the user program does not agree with the address actually accessed.
The user must therefore make sure that the address grid and the initial addresses are
set correctly for all modules.
For this reason, check the settings on the IM 306, AI 463 and CP 523 modules.
EWA 4NEB 811 6148-02