S5-115F Manual
Technical Specifications
8
Technical Specifications
8.1
General Technical Specifications
Climatic
Environmental Conditions
Temperature
Operating
- open design
Air intake temperature
(measured at the bottom
of the modules)
0 to+55° C
- cabinet design
(Where cabinet design is concerned, the dissipatible heat
loss depends on the type of construction, the ambient
temperature, and the arrangement of the devices.)
Air intake temperature
(measured at the bottom
of the modules)
0 to+55° C
Nonoperating
- 40 to+85° C
Temperature change
- operating
max. 10 K / h
- nonoperating
max. 20 K / h
Relative humidity
- operating
95% (acc. to DIN 40040)
- nonoperating
95% (noncondensing)
Atmospheric pressure
- operating
860 to 1060 hPa
1
- nonoperating
660 to 1060 hPa
1
Pollutants
- SO
2
0.5 ppm,
(rel. humidity 60%,
noncondensing)
- H
2
S
0.1 ppm,
(rel. humidity 60%,
noncondensing)
Mechanical
Environmental Conditions
Vibration
to IEC 68-2-6
- tested with
10 to 57 Hz,
(const. amplitude 0.15 mm)
57 to 150 Hz,
(const. acceleration 2 g)
Shock
to IEC 68-2-27
- tested with
12 shocks
(half sine 15 g / 11 msec.)
Free fall
to IEC 68-2-32
- tested with
height of fall 1 m (3.3 ft.)
1 For use under 900 hPa (=1000 m above sea-level), check with the manufacturer on the cooling requirements.
EWA 4NEB 811 6148-02
8-1