Rules Governing the Use of the S5-115F
S5-115F Manual
Note
If the validity of your input data cannot be checked, you cannot make operator entries
with the programmer.
Filter program for parameter entry DB
Note
The filter program for the parameter entry DB must be approved by the inspector.
10.19
SINEC L1 LAN
Note the following points when operating a SINEC L1 LAN:
•
The SINEC L1 master may be any PLC of the U range.
•
The SINEC L1 master must have no interrupt list.
•
The SINEC L1 master may not initiate safety-related actions (e.g. START/STOP of a slave).
•
A description of the data flow via the SINEC L1 LAN must be provided for the individual
acceptance test. The test is made easier if I/O signals, for example, are not transmitted along
several consecutive SINEC paths.
•
When transmitting analog values, the accompanying ”Error” and ”Overrange” bits must also
be transmitted.
•
The BT 777 transceiver must be supplied via separate power supply units.
•
If you want to generate a mailbox in a data block, you must create the data block either
- in the restart OBs (OB 21 and OB 22) or
- using the programmer.
•
COM 530 may not be used in safety mode.
The keylock switch on the relevant programmer must be locked.
•
You can find additional information in section 7.2.3.
•
If an S5-115F slave is to be shut down in a SINEC L1 network, the power supply of the relevant
transceiver must be switched off.
•
Program the SINEC L1 master (CP 530 in the higher-level S5-115U, S5-135U, S5-150U or
S5-155U) in such a way that the length of messages to a slave S5-115F matches the configured
length of the Receive mailbox.
You must extend shorter messages to the length of the Receive mailbox.
•
High-level protection of the destination slave number is always necessary if you configure
more than two slaves with the same mailbox length. The S5-115F enters the information for
error detection and correction in the first byte of the mailbox. You must not alter the error
detection and correction information.
•
High-level protection of the destination slave number and a message change byte are always
necessary if you want to send broadcast messages. The S5-115F enters the information for
error detection and correction in the first two bytes of the mailbox. You must not alter the
error detection and correction information.
10-68
EWA 4NEB 811 6148-02