Technical Specifications
S5-115F Manual
IEC / VDE
Safety Information
Degree of protection
to IEC 529
- type
IP 20
- class
to IEC 536
Insulation rating
- between electrically
independent circuits
and
with circuits connected
by a central grounding
point
to VDE 0160
- between all
circuits
and
central grounding point
(standard mounting rail)
to VDE 0160
Test voltage
sine, 50 Hz
for a rated
voltage V
e
of the
circuits (AC / DC)
V
e
= 0 to 50 V
500 V
V
e
= 50 to 125 V
1250 V
V
e
= 125 to 250 V
1500 V
Impulse voltage
to IEC 255-4
for a rated
voltage V
e
of the
circuits (AC / DC)
V
e
= 0 to 50 V
1 kV, 1.2 / 50
µ
s
V
e
= 50 to 125 V
1 kV, 1.2 / 50
µ
s
V
e
= 125 to 250 V
3 kV, 1.2 / 50
µ
s
RI specification
to VDE 0871
- limit class
A
Note:
AC output modules
are not interference suppressed!
Electromagnetic Compatibility (EMC)
Noise Immunity
Damped oscillatory wave test
to IEC 255-4
- AC power supply modules
2.5 kV
- DC power supply modules
1 kV
- output 24 V DC
1 kV
- input 115 V AC / 230 V AC
2.5 kV
- digital input/output modules
2.5 kV
- analog input/output modules
1 kV
- communications interfaces
1 kV
Fast transient burst test
to IEC 65
(Sec) 87
- power supply modules
2 kV
- digital input/output modules
2 kV
- analog input/output modules
1 kV
- communications interfaces
1 kV
Electrostatic discharge test
to IEC 801-2
(Discharge to all
parts accessible to
the operator in
normal operation)
- power supply modules
5 kV
- digital input/output modules
5 kV
- analog input/output modules
5 kV
- communications interfaces
5 kV
Radiated electromagnetic field test
to IEC 801-3
- test field strength
3 V/m
Fast transient burst
to IEC 801-4
- power supply modules
- digital input/output modules
- analog input/output modules
- communications interfaces
8-2
EWA 4NEB 811 6148-02